Docsity
Docsity

Prepare for your exams
Prepare for your exams

Study with the several resources on Docsity


Earn points to download
Earn points to download

Earn points by helping other students or get them with a premium plan


Guidelines and tips
Guidelines and tips

TFM02 - FEL B Exam Questions and Answers (Verified Answers) Latest Update 2024, Exams of Nursing

TFM02 - FEL B Exam Questions and Answers (Verified Answers) Latest Update 2024TFM02 - FEL B Exam Questions and Answers (Verified Answers) Latest Update 2024

Typology: Exams

2024/2025

Available from 11/23/2024

expertnurse01
expertnurse01 🇺🇸

2.3

(10)

776 documents

1 / 14

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
TFM02 - FEL B Exam Questions and Answers (Verified
Answers) Latest Update 2024
The hydrostatic test interval for a dry chemical extinguisher with a stainless
steel shell is every __ years - correct answers 5
The hydrostatic test interval for a stored-pressure water, water mist, loaded
stream, and/or antifreeze is __ years - correct answers 5
The hydrostatic test interval for a Wetting agent extinguisher is __ years. -
correct answers 5
The Hydrostatic test interval for a AFFF (aqueous film-forming foam)
extinguisher is __ years. - correct answers 5
The Hydrostatic test interval for a FFFP (film-forming fluoroprotein foam)
extinguisher is __ years. - correct answers 5
The hydrostatic test interval for a Carbon Dioxide extinguisher is __ years. -
correct answers 5
The hydrostatic test interval for a Wet Chemical extinguisher is __ years. -
correct answers 5
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe

Partial preview of the text

Download TFM02 - FEL B Exam Questions and Answers (Verified Answers) Latest Update 2024 and more Exams Nursing in PDF only on Docsity!

Answers) Latest Update 2024

The hydrostatic test interval for a dry chemical extinguisher with a stainless steel shell is every __ years - correct answers ✅ 5 The hydrostatic test interval for a stored-pressure water, water mist, loaded stream, and/or antifreeze is __ years - correct answers ✅ 5 The hydrostatic test interval for a Wetting agent extinguisher is __ years. - correct answers ✅ 5 The Hydrostatic test interval for a AFFF (aqueous film-forming foam) extinguisher is __ years. - correct answers ✅ 5 The Hydrostatic test interval for a FFFP (film-forming fluoroprotein foam) extinguisher is __ years. - correct answers ✅ 5 The hydrostatic test interval for a Carbon Dioxide extinguisher is __ years. - correct answers ✅ 5 The hydrostatic test interval for a Wet Chemical extinguisher is __ years. - correct answers ✅ 5

Answers) Latest Update 2024

The hydrostatic test interval for a Dry chemical, stored-pressure, with mild steel shells, brazed brass shells, or aluminum shells is __ years. - correct answers ✅ 12 The hydrostatic test interval for a Dry chemical, cartridge- or cylinder- operated, with mild steel shells is __ years. - correct answers ✅ 12 The hydrostatic test interval for a Halogenated Agent extinguisher is __ years. - correct answers ✅ 12 The hydrostatic test interval for a Dry powder, stored-pressure, cartridge- or cylinder- operated, with mild steel shells extinguisher is __ years. - correct answers ✅ 12 The maintenance internal examination for a stored-pressure loaded stream and antifreeze is __ years. - correct answers ✅ 1 The maintenance internal examination for a Pump tank water and pump tank, calcium chloride based extinguisher is __ years. - correct answers ✅ 1

Answers) Latest Update 2024

The maintenance internal examination for a Stored-pressure dry chemical, with stainless steel shells extinguisher is __ years. - correct answers ✅ 5 The maintenance internal examination for a Carbon dioxide extinguisher is __ years. - correct answers ✅ 5 The maintenance internal examination for a Wet chemical extinguisher is __ years. - correct answers ✅ 5 The maintenance internal examination for a Dry chemical stored-pressure, with mild steel shells, brazed brass shells, and aluminum shells is __ years. - correct answers ✅ 6 The maintenance internal examination for a Halogenated Agent extinguisher is __ years. - correct answers ✅ 6 What does ANSI stand for? - correct answers ✅American National Standards Institue

Answers) Latest Update 2024

High Pressure Cylinders containing nitrogen, compressed air, carbon dioxide, or other compressed gases at a service pressure higher than ___ psi at 70 degree Fahrenheit - correct answers ✅ 500 Low Pressure Cylinders containing fire-extinguishing agent, nitrogen, compressed air, or other compressed gases at a service pressure of ___ psi or lower at 70 degree Fahrenheit - correct answers ✅ 500 What are Halgoenated Agents? - correct answers ✅Halogen agents are clean agents. Including bromochlorodifluoromethane (Halon 1211), and bromotrifluoromethane (Halon 1301) What does HMIS stand for? - correct answers ✅Hazardous Materials Identification Sheet The following information shall be on a fire extinguisher tag - correct answers ✅1. The content's product name as it appears on the manufacturers Material Safety Data Sheet (MSDS)

  1. List of the HMIS

Answers) Latest Update 2024

What hazards does a Class D Fire Extinguisher Protect? - correct answers ✅Class D fires are fires in combustible metals, such as magnesium, titanium, zirconium, sodium, lithium, and potassium. What hazards does a Class K Fire Extinguisher Protect? - correct answers ✅Class k fires are fires in cooking appliances that involve combustible cooking media (vegetable or animal oils and fats. Use of halon agent fire extinguishers shall be limited to applications where a ______ _______ is necessary to extinguish fire efficiently without damaging the equipment. - correct answers ✅Clean Agent Wheeled fire extinguishers shall be considered for hazard protection in areas in which a fire risk assessment has shown _______. - correct answers ✅High hazard areas are present. Wheeled Fire extinguishers has the following features: - correct answers ✅1. High agent flow rate

  1. Increased agent stream range
  2. Increased agent capacity

Answers) Latest Update 2024

Extinguishers for Pressurized Liquid and Pressurized Gas fires: - correct answers ✅Large-capacity dry chemical extinguishers of 10 lb or greater and with a discharge rate of 1 lb/sec or more shall be selected to protect these hazards. Extinguishers for Three-Dimensional Fires - correct answers ✅Large-capacity dry chemical extinguishers of 10 lb or greater and with a discharge rate of 1lb/sec or more shall be selected to protect these hazards. Fire extinguishers having a gross weight not exceeding 40lb shall be installed so that the top of the fire extinguisher is not more than __ ft above the floor

  • correct answers ✅ 5 FIre extinguishers having a gross weight greater than 40 lb (except whelled types) shall be installed so that the top of the fire extinguisher is not more than __ ft above the floor - correct answers ✅3 1/2 feet

Answers) Latest Update 2024

____ AFFF or FFFP fire extinguishers of at least 1.6 gal capacity shall be permitted to be used to fulfill ordinary hazard requirements. - correct answers ✅Two Class K Fire Extinguishers shall be located so that the maximum travel distances shall not exceed __ ft from the hazard to the extinguishers. - correct answers ✅30 Feet Class D Fire Extinguishers shall be located not more than __ ft of travel distance from the Class D hazard. - correct answers ✅ 75 Fire extinguishers removed from service shall be _______ replaced with extinguishers that are suitable for the type of hazard being protected and shall be of at least equal rating. - correct answers ✅immediately Stored-pressure types of fire extinguishers containing a loaded stream agent shall be disassembled on an _____ basis and subjected to complete maintenance. - correct answers ✅Annual

Answers) Latest Update 2024

The loaded stream charge _____ be permitted to be recovered and re-used, provided it is subjected to agent analysis. - correct answers ✅shall The extinguishing agent of cartridge- or cylinder-operated extinguishers shall be internally examined ________. - correct answers ✅Annualy Wetting agent extinguishers shall be disassembled on an _____ basis and subjected to complete maintenance. - correct answers ✅annual Pump tank extinguishers shall be internally examined ______ - correct answers ✅annually Annual internal examination shall not be required for ____________ - correct answers ✅1. Nonrechargeable fire extinguishers

  1. Carbon Dioxide Fire extinguishers
  2. Stored-pressure fire extinguisher A Conductivity test shall be conducted _____ on all carbon dioxide hose assemblies. - correct answers ✅annually

Answers) Latest Update 2024

True or False? Wet chemical or water mist agent shall be discarded and replaced at the hydrostatic test interval. - correct answers ✅True True or False? Only the agent specified on the extinguisher nameplate shall be used for recharge. - correct answers ✅True A regulated source of pressure, set no higher than __________ psi above the operating (service) pressure, shall be used to pressurize fire extinguishers. - correct answers ✅ 25 Test pressure gauges shall be capable of indicating __ to ___ percent of the test pressure. - correct answers ✅90, 110 The hydrostatic test label should have all of the following - correct answers ✅1. Month and year the test was performed, indicated by a perforation, such as is done by a hand punch

  1. Test pressure used.
  2. Name or initials of the person performing the test and name of the agency performing the test.

Answers) Latest Update 2024

The hydrostatic test label shall meet the following criteria: - correct answers ✅1. Sized at a maximum of 2in X 3 1/2 in

  1. Affixed by a heatless product
  2. Self-destructs when removed from a fire extinguisher cylinder shell
  3. Made of a durable, weatherproof material with a pressure sensitive adhesive. What does AFFF mean? - correct answers ✅Aqueous Film Forming Foam What does FFFP mean? - correct answers ✅Film Forming Fluoroprotein Foam Dry chemical and dry powder in cartridge- or cylinder-operated extinguishers are examined _______. - correct answers ✅annually The extinguishing agent in liquid charge- type AFFF and FFFP extinguishers is replaced every __ years, and an internal examination (teardown) is normally conducted at that time. - correct answers ✅ 3