Docsity
Docsity

Prepare for your exams
Prepare for your exams

Study with the several resources on Docsity


Earn points to download
Earn points to download

Earn points by helping other students or get them with a premium plan


Guidelines and tips
Guidelines and tips

iec year 2 part 3 EXAM TEST BANK WITH ALL VERSIONS OF THE EXAM WITH ALLMODULES COVERED |, Exams of Electrical Engineering

1. When a large service is built, CT cans are utilized. These enclosures contain ___ transformers. A. Voltage B. Power C. Current D. Step-down ✅ Correct Answer: C. Current Rationale: CT cans house Current Transformers used for metering and protection in large services. 2. Large dry-type distribution transformer enclosures have steel bottoms that are punched for ___. A. Conduits B. Wires C. Screws D. Ventilation ✅ Correct Answer: D. Ventilation Rationale: Per NEC, ventilation holes dissipate heat from the transformer. 3. When a transformer’s windings are encapsulated, the resin encapsulation ___. A. Protects against moisture B. Reduces sound C. Increases mechanical strength D. All of the above ✅ Correct Answer: D. All of the above Rationale: Resin encapsulation provides insulation, noise reduction, and protection.

Typology: Exams

2024/2025

Available from 06/28/2025

sammy-blazer
sammy-blazer 🇺🇸

1

(1)

644 documents

1 / 39

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
iec year 2 part 3 EXAM TEST BANK
WITH ALL VERSIONS OF THE EXAM
WITH ALLMODULES COVERED |
ACCURATE AND VERIFIED QUESTIONS
AND ANSWERS FOR GUARANTEED
PASS| LATEST UPDATE
1. When a large service is built, CT cans are utilized. These enclosures contain
___ transformers.
A. Voltage
B. Power
C. Current
D. Step-down
Correct Answer: C. Current
Rationale: CT cans house Current Transformers used for metering and protection in
large services.
2. Large dry-type distribution transformer enclosures have steel bottoms that are
punched for ___.
A. Conduits
B. Wires
C. Screws
D. Ventilation
Correct Answer: D. Ventilation
Rationale: Per NEC, ventilation holes dissipate heat from the transformer.
3. When a transformer’s windings are encapsulated, the resin encapsulation ___.
A. Protects against moisture
B. Reduces sound
C. Increases mechanical strength
D. All of the above
Correct Answer: D. All of the above
Rationale: Resin encapsulation provides insulation, noise reduction, and protection.
4. A transformer enclosure that is ventilated ___ air from outside the enclosure to
circulate through it.
A. Blocks
B. Filters
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12
pf13
pf14
pf15
pf16
pf17
pf18
pf19
pf1a
pf1b
pf1c
pf1d
pf1e
pf1f
pf20
pf21
pf22
pf23
pf24
pf25
pf26
pf27

Partial preview of the text

Download iec year 2 part 3 EXAM TEST BANK WITH ALL VERSIONS OF THE EXAM WITH ALLMODULES COVERED | and more Exams Electrical Engineering in PDF only on Docsity!

iec year 2 part 3 EXAM TEST BANK

WITH ALL VERSIONS OF THE EXAM

WITH ALLMODULES COVERED |

ACCURATE AND VERIFIED QUESTIONS

AND ANSWERS FOR GUARANTEED

PASS| LATEST UPDATE

1. When a large service is built, CT cans are utilized. These enclosures contain ___ transformers. A. Voltage B. Power C. Current D. Step-down ✅ Correct Answer: C. Current Rationale: CT cans house Current Transformers used for metering and protection in large services. 2. Large dry-type distribution transformer enclosures have steel bottoms that are punched for ___. A. Conduits B. Wires C. Screws D. Ventilation ✅ Correct Answer: D. Ventilation Rationale: Per NEC, ventilation holes dissipate heat from the transformer. 3. When a transformer’s windings are encapsulated, the resin encapsulation ___. A. Protects against moisture B. Reduces sound C. Increases mechanical strength D. All of the above ✅ Correct Answer: D. All of the above Rationale: Resin encapsulation provides insulation, noise reduction, and protection. 4. A transformer enclosure that is ventilated ___ air from outside the enclosure to circulate through it. A. Blocks B. Filters

C. Does not allow D. Does allow ✅ Correct Answer: D. Does allow Rationale: Ventilated enclosures are designed to allow airflow for cooling.

5. An example of an autotransformer is a ___. A. Buck-boost transformer B. Variac C. Isolation transformer D. Both A and B ✅ Correct Answer: D. Both A and B Rationale: Buck-boost and variac types use a common winding like autotransformers. 6. A step-down transformer’s secondary winding is connected to ___. A. Ground B. The supply C. The load D. The neutral ✅ Correct Answer: C. The load Rationale: The secondary supplies power to the load at a lower voltage. 7. An ___ has no direct electrical connection between primary and secondary windings. I. Autotransformer II. Isolation transformer A. I only B. II only C. Both I and II D. Neither ✅ Correct Answer: B. II only Rationale: Only isolation transformers have electrically isolated windings. 8. Dry-type transformer insulation is based on an ambient temperature of ___°C. A. 25 B. 30 C. 40 D. 55 ✅ Correct Answer: C. 40 Rationale: Industry standard insulation class is based on 40°C ambient. 9. A transformer with a ___ enclosure is permitted to be installed inside a building. A. Ventilated

14. When operated within its ratings, a transformer can be expected to operate for about ___ years. A. 10– 15 B. 20– 25 C. 5– 8 D. 30– 35 ✅ Correct Answer: B. 20– 25 Rationale: Transformers are typically designed for 20–25 years of service when not overloaded. 15. A transformer requires 32 amps at 480 volts on the primary to deliver 120-volt power to a 14.6 kW load. The efficiency of this transformer is ___%. A. 90 B. 92 C. 95 D. 98 ✅ Correct Answer: C. 95 Rationale: Efficiency = Output/Input power = 14.6 kW / (480V × 32A) ≈ 0.95 or 95%. 16. A new transformer must be sized at 125% of the existing 79.2 kVA load. The minimum calculated size is ___ kVA. A. 89 B. 92 C. 99 D. 105 ✅ Correct Answer: C. 99 Rationale: 79.2 × 1.25 = 99 kVA. 17. Turns ratio can be written as ___. A. Primary:Secondary B. Voltage ratio C. Number of turns D. Any of these ✅ Correct Answer: D. Any of these Rationale: The turns ratio can be expressed in various forms depending on context— number of turns, voltage ratio, or current ratio. 18. A 120 VA load is the only load connected to the secondary of a 250 VA transformer. To supply this load, the transformer must be supplied with at least ___ VA of power on the primary. A. 250 B. 200 C. 120 D. 100

Correct Answer: C. 120 Rationale: The primary must provide at least what the load demands—120 VA.

19. A CT with a current ratio of 500:1 is used in a metering circuit. If the meter shows 67 mA, the actual current is ___ amps. A. 33. B. 67 C. 500 D. 134 ✅ Correct Answer: A. 33. Rationale: 0.067 A × 500 = 33.5 A in the primary circuit. 20. A transformer has a 240 V primary and a 120 V secondary. A 10 A load on the secondary draws how much primary current? A. 5 A B. 10 A C. 15 A D. 20 A ✅ Correct Answer: A. 5 A Rationale: Power is conserved: 240 V × I = 120 V × 10 A → I = 5 A. 21. Transformers are rated in ___ indicating maximum output power. A. kW B. HP C. VA D. V ✅ Correct Answer: C. VA Rationale: Transformers are rated in Volt-Amperes (VA) because they handle apparent power. 22. A 1Ø transformer rated at 500 VA can supply ___ amps at 120 volts. A. 2. B. 3. C. 4. D. 5. ✅ Correct Answer: C. 4. Rationale: Current = Power / Voltage = 500 / 120 = 4.17 A. 23. A 120 V primary, 12 V secondary transformer has a turns ratio of ___ to 1. A. 5 B. 10 C. 15 D. 20

Correct Answer: B. 5: Rationale: 120 / 24 = 5:1 ratio.

29. A 15 kVA transformer supplying an 11.5 kW load at 120 V delivers ___ amps. A. 85. B. 95. C. 100 D. 120 ✅ Correct Answer: B. 95.83 A Rationale: I = P / V = 11,500 / 120 = 95.83 A. 30. Which statement is true about transformers? A. Voltage and current are inversely proportional B. Power in primary equals power in secondary (minus losses) C. Both A and B D. Neither A nor B ✅ Correct Answer: C. Both A and B Rationale: Transformer principles include conservation of power and inverse voltage- current relationship. 31. A transformer with 120 V primary and 24 V secondary receives only 100 V input. The output voltage is ___. A. 20 V B. 18 V C. 22 V D. 24 V ✅ Correct Answer: A. 20 V Rationale: Proportional voltage drop: (100/120) × 24 = 20 V. 32. Using an ohmmeter between transformer terminals X1 and H2, the reading would be: A. 0 Ω B. Infinite (OL) C. 12 Ω D. 120 V ✅ Correct Answer: B. Infinite (OL) Rationale: Primary and secondary are isolated, so resistance is infinite (no continuity). 33. A transformer rated 130 V primary, 16 V secondary receives 110 V. Output voltage is ___. A. 12 B. 13. C. 16

D. 10

Correct Answer: B. 13.54 V Rationale: (110 / 130) × 16 = 13.54 V.

34. A 120 V primary with 24 V secondary and 2 A primary current yields secondary current of: A. 2 A B. 4 A C. 10 A D. 12 A ✅ Correct Answer: C. 10 A Rationale: Power is constant → 120 × 2 = 240 W; secondary I = 240 / 24 = 10 A. 35. A transformer delivers 332 A at 240 V. It is supplying ___ kVA. A. 72 B. 79. C. 84 D. 100 ✅ Correct Answer: B. 79.68 kVA Rationale: kVA = (332 × 240) / 1000 = 79.68 kVA. 36. A 120 V primary, 16 V secondary transformer with 1.1 A primary current implies ___ A secondary current. A. 5 B. 8. C. 6 D. 10 ✅ Correct Answer: B. 8.25 A Rationale: 120 × 1.1 = 132 W; 132 / 16 = 8.25 A. 37. Two 120/240 V transformer secondary windings connected for 240 V are in ___. A. Parallel B. Series C. Wye D. Delta ✅ Correct Answer: B. Series Rationale: Series connection combines voltages for 240 V operation. 38. A 25 kVA 120/240 V transformer delivers ___ amps at 240 V. A. 62. B. 83. C. 104

A. 1

B. 2.

C. 5

D. 10

Correct Answer: B. 2. Rationale: 2.5% is standard step size in tap settings for fine voltage adjustment.

44. For a 1Ø transformer with dual-voltage secondary, power rating is total power ___ can supply. A. One winding B. The higher voltage side C. The lower voltage side D. Both secondary windings ✅ Correct Answer: D. Both secondary windings Rationale: The total transformer rating includes power from both windings. 45. For a 1Ø transformer with dual-voltage secondary, the voltages induced in each winding are equal. A. True B. False ✅ Correct Answer: A. True Rationale: Windings are identical; voltages are the same unless connected differently. 46. Which secondary transformer connection (Figure 215.52) supplies correct voltage to a 120 V load? A. I B. II C. III D. IV ✅ Correct Answer: B. II Rationale: Connection II shows parallel windings for 120 V output. 47. Which secondary transformer connection (Figure 215.52) supplies correct voltage to a 240 V load? A. I B. II C. III D. IV ✅ Correct Answer: A. I Rationale: Connection I shows series configuration for 240 V output. 48. When the ___ voltage differs from the rated voltage, transformer taps can be used to correct output voltage.

A. Secondary B. Primary C. Load D. Neutral ✅ Correct Answer: B. Primary Rationale: Taps on the primary side adjust for input voltage variation.

49. Refer to Figure 216.21. The transformer feeding MDP must supply ___ volts to the Main Distribution Panel. A. 208 B. 240 C. 120/ D. 480 ✅ Correct Answer: C. 120/ Rationale: Based on panel and switch loads listed, a 1Ø 3W 120/240 V supply is needed. 50. A 480–120/240 V transformer is supplied with 496 V. The expected line-to- neutral output voltage is ___. A. 120 V B. 122 V C. 124 V D. 126 V ✅ Correct Answer: C. 124 V Rationale: Higher input raises output proportionally: (496/480) × 120 = 124 V. 51. Voltage taps on the transformer primary are used when input voltage is ___ rated voltage. A. Equal to B. Higher than C. Lower than D. Either B or C ✅ Correct Answer: D. Either B or C Rationale: Taps adjust for both overvoltage and undervoltage conditions. 52. A 240/480 V primary – 120/240 V secondary transformer can connect to a 2- pole breaker in a ___ panelboard and still deliver nameplate-rated voltage. A. 120 V B. 240 V C. 480 V D. B or C only ✅ Correct Answer: D. B or C only

___ surrounds the windings in typical 75 kVA dry-type distribution transformers. - Ans - Air OSHA ___ sets forth standards for fall protection training. - Ans - 1926. OSHA has standards for which of the following? - Ans - both a and b The most frequently cited OSHA construction standards change ___ from year to year. - Ans - little The general duty clause of the OSHA standard requires ___ employer(s) to provide to each of his employees, a place of employment that is free of hazards which are likely to cause death or serious harm to his employees. - Ans - each OSHA 1926.451 covers ___. - Ans - scaffold access The Powered Industrial trucks standard covers ___ plus operator training and operation.I. forklifts II. motorized hand trucks III. material handling equipment - Ans - I, II & III The OSHA ___ standard is violated more than any other in construction work and even has two standards. - Ans - Fall Protection Many three-phase generators can be connected to deliver output voltage configurations such as ___. - Ans - both a and b The rated power output (capacity) of a transformer is given on the nameplate in ___. - Ans - kVA In three-phase systems, the voltage between any two ungrounded conductors is equal. This voltage is known as ___. - Ans - any of these Which of the following statements is true of wye-configured voltage systems? - Ans - Icoil = Iline A three-phase generator has three sets of magnets on the rotor. These are mounted so that they ___. - Ans - are offset 120° from each other Which of the following statements is true of delta-configured voltage systems? - Ans - Icoil = Iline / 1.

The following are examples of a slash-rated three-phase system except for ___. - Ans - 480V three-phase, three-wire Three-phase, four-wire systems can provide power to the following loads: - Ans - all of these If the higher voltage of a slash-rated three-phase voltage system equals twice the lower voltage, the system is ___. - Ans - delta-connected When a 3Ø, 4-W supply system delivers 120/208 volts, the system is ___ connected. - Ans - wye A 480-volt 3-phase circuit is connected to the delta primary of a 480 to 240-volt 3-phase transformer. The voltage across any one primary winding is ___ volts. - Ans - 480 Which of the following is a type of electric power generating plant? - Ans - All of these Substations are used to ___. - Ans - either a or b When a 3Ø, 4-W supply system delivers 120/240 volts, the system is ___ connected. - Ans - delta When a 3Ø, 4-W supply system (typically a transformer) delivers 120/240 volts, the system has line-to-line voltages that are ___ volts. - Ans - 240 When a 3Ø, 4-W supply system (typically a transformer) delivers 120/240 volts, the system has BØ-to-neutral voltages that are ___ volts. - Ans - 208 Inverters are required to convert the output energy from ___ to AC. - Ans - solar arrays Which of these are typical high transmission voltages? - Ans - 230 kV When a 3Ø, 3-W supply system delivers 240 volts, the system is ___ connected. - Ans - delta When a 3Ø, 4-W supply system delivers 277/480 volts, the system has line-to-line voltages that are ___ volts. - Ans - 480 If the output of a 3Ø generator is 240 volts, line-to-line, and it has a neutral connection, this is a ___ system. - Ans - 3Ø, 4-W When a 3Ø, 4-W supply system delivers 277/480 volts, the system is ___ connected. - Ans - wye

A 208-volt, 17.2 KVA, single-phase load is connected to a 120/208-volt, three-phase, 4wire panel. The load will draw ___ amps at the applied voltage. - Ans - 82. A certain 3-phase load draws 27.8 amps and is operating on a circuit that is fed from a 120/240-volt 3-ph, 4-W panelboard. This load is using ___ kVA of power. - Ans - 11. A 3Ø 240-volt load is supplied power by a 100 KW generator. The nameplate rating on the load is 59.2 KVA. The line (circuit) conductors between the generator and the load will be carrying ___ amps. - Ans - 142 A 3Ø, 480-volt, 45 KVA, wye-connected load draws ___ a 3Ø, 480-volt, 45 KVA, deltaconnected load. - Ans - the same line current as A three-phase 69 KVA load will be connected to a circuit that is fed from a 3-pole breaker in a 120/240-volt 3Ø, 4-wire panel. This load will draw ___ amps of current through each circuit conductor. - Ans - 166 A certain 3-phase load draws 37.3 amps and is operating at 208 volts. This load is using ___ KVA of power. - Ans - 13. Three-phase loads of 16, 42, and 75 amps are fed from a 240-volt panel. This total 3Ø load is ___ kVA. - Ans - 55. The ___ shall determine if the walking/working surface has strength and structural integrity to support employees safely. - Ans - employer Each employee at the edge of ___ or similar excavation 6 feet or more in depth shall be protected from falling by guardrail systems, fences, or barricades.I. a pit II. a well III. a shaft - Ans - I or II or III Each employee in a hoist area shall be protected from falling 6 feet or more to a ___ by guardrail systems or personal fall arrest systems. - Ans - lower level When working over dangerous equipment that one could fall onto or into, one must be protected by guardrail systems, ___, or personal fall arrest systems. - Ans - machine guards Falls are the number ___ cause of construction deaths. - Ans - one Each employee on a walking/working surface with an unprotected side or edge which is 6 feet or more to a lower level shall be protected from falling by use of ___ systems.I. personal fall arrest II. guardrail III. safety net - Ans - I or II or III

The OSHA subpart on Fall Protection has many ___ that outline numerous methods to accomplish safe means to work at heights. - Ans - requirements If an employee can fall through a ___ 6 feet or more to a lower level the employee has to be protected by personal fall arrest systems, covers over the holes, or guardrail systems. - Ans - hole A ___ connection requires that the single-phase transformers be interconnected so that X1 of one transformer is connected to X2 of the next. - Ans - delta A(n) ___ delta is a variation of a three-phase, four-wire system that only utilizes two transformers. - Ans - open When equipment, a system, or a circuit has a delta or wye designation, the equipment, system, or circuit is ___. - Ans - three-phase In a three-phase four-wire delta system, the B-phase conductor is known as the ___ and is connected to the middle busbar in the panel. - Ans - high-leg If 120-volt loads are required to be connected to a delta transformer, one of the three output coils has a ___ so that two 120-volt outputs are available. - Ans - center-tap When the supply voltage is higher or lower than the nameplate rated primary voltage of a transformer ___. - Ans - it will result in a higher or lower-than-nameplate rated secondary voltage The connected load on the secondary of a transformer causes current to flow in the ___. - Ans - all of these In a three-phase transformer, if a voltage higher than the nameplate rated voltage is applied to the primary, a voltage ___ the nameplate rated secondary voltage will be delivered to a load. - Ans - higher than When transformers are installed to adjust voltage for a customer's needs, they can be configured to ___. - Ans - either of these If a transformer has a delta primary and a wye secondary, the transformer is referred to as a ___ transformer. - Ans - delta-wye In a corner-grounded delta, the grounded conductor is referred to as the ___. - Ans - dead man's leg If the load connected to the secondary of a delta-connected transformer is balanced, the coil currents are equal in each of the three windings. - Ans - True

Figure 220.401 Refer to Figure 220.401. The transformer bank has each of its secondary ("X") windings connected in ___. - Ans - series Figure 220.402 Each transformer in the bank, shown in Figure 220.402, is rated to deliver 120/240 when rated primary voltage is applied. Which diagram shows the correct connections for a 120/240-volt, 3-ph, 4-wire secondary? - Ans - I only Where a delta bank of three transformers is installed to serve a load that is comprised mostly of 120-volt loads (balanced), each power transformer must supply ___ required by the 120-volt loads. - Ans - about a third of the current When a 3Ø, 4-W supply system (typically a transformer) delivers 120/240 volts, the system has coil (or winding) voltages that are ___ volts. - Ans - 240 A ___ output could be produced by connecting three individual 240 ´ 480 - 120/240 volt single-phase transformers into a bank.I. 240 volt 3Ø, 3-wire II. 120/240 volt 3Ø, 4 wire - Ans - either I or II A 3Ø transformer supplies 120/240 volts to a 3Ø, 4-wire panelboard. From the breaker in space ___, there will be 208 volts to ground (or neutral). - Ans - 10 Scenario 220.21A 3Ø transformer bank supplies 120/240 volts to a 3Ø, 4-wire panelboard. There is a 30 kVA 3Ø load connected to a 3-pole breaker in spaces 1- 3 - 5. There is a 240-volt 15 kW load connected to a 2-pole breaker in spaces 2-4. There is a 120 - volt 10 kW load connected to a 1-pole breaker in space 6. Refer to Scenario 220.21. If all the loads are operating and a clamp-on ammeter were placed around the AØ feeder conductor to the panel, there should be ___ amps of current flowing in the feeder conductor. - Ans - 134. Scenario 220.23 A closed-delta bank of transformers delivers 120/240-volt power to several loads. The 1-phase loads are drawing 120 amps on AØ and 120 amps on CØ. The bank is also supplying power to a 3Ø load that draws 46 amps.Refer to Scenario 220.23. The approximate calculated size required for the "lighting" transformer(s) has a rating of ___ KVA. - Ans - 26 When a 120/240-volt 3Ø, 4-W supply system (typically a transformer) delivers power to a load, the line current equals ___. - Ans - Icoil (or winding) x 1. ___-connected primaries are more common. - Ans - Delta A bank of three 100 KVA transformers is delivering 120/240 volts to a building service. This bank can deliver ___ amps of current to the service if one of the transformers goes out. - Ans - 417

When a 120/240-volt, 3Ø, 4-W open-delta bank of transformers delivers power to a load, the line voltage equals ___. - Ans - Ecoil (or winding) An open-delta bank of transformers uses 100 KVA transformers. This bank can deliver a maximum of ___ kVA of power. - Ans - 173 When a 120/240-volt, 3Ø, 4-W open-delta bank of transformers delivers power to a load, the line current equals ___. - Ans - Icoil (or winding) When a 120/240-volt, 3Ø, 4-W open-delta bank of transformers delivers power to a load, the BØ-to-neutral voltage is ___ volts. - Ans - 208 Refer to Figure 220.301 where the secondary voltage is 240 volts. This is a(n) ___ transformer bank. - Ans - open delta When a 120/240-volt, 3Ø, 4-W open-delta bank of transformers delivers power to a load, the AØ-to-neutral voltage is ___ volts. - Ans - 120 An open-delta bank of transformers delivers ___ power. - Ans - 3Ø When a 120/240-volt, 3Ø, 4-W open-delta bank of transformers delivers power to a load, the AØ-to-CØ voltage is ___ volts. - Ans - 240 Three-phase loads of 16, 42, and 75 amps are fed from a 208-volt panel. This total 3Ø load is ___ KVA. - Ans - 47. When a 120/208-volt, 3Ø, 4-W supply system (typically a transformer) delivers power to a load, the line voltage equals ___. - Ans - Ecoil (or winding) x 1. When a 277/480-volt, 3Ø, 4-W supply system (typically a transformer) delivers power to a load, the coil (or winding) current equals ___. - Ans - IL When a 120/208-volt, 3Ø, 4-W supply system (typically a transformer) delivers power to a load, the coil (or winding) voltage equals ___. - Ans - EL ÷ 1. A 3Ø, 45 KVA load will be supplied power by a 3Ø, 480 to 120/208-volt "Y" transformer bank. This transformer bank must have a 3Ø rating of at least ___ KVA. - Ans - 45 When a 3Ø, 4-W supply system (typically a transformer) delivers 277/480 volts, the system has line-to-neutral voltages that are ___ volts. - Ans - 277 If the output of a 3Ø generator is 208 volts, line-to-line, and it has a neutral connection, this is a ___ system. - Ans - 3Ø, 4-W