Detailed solutions to the iec second year final exam questions for electrical engineering, covering topics such as conduit sizing, box requirements, circuit breaker selection, and load calculations. The correct answers to all questions, making it an invaluable resource for students preparing for their exams.
Typology: Exams
1 / 15
This page cannot be seen from the preview
Don't miss anything!
You are to install IMC between two equipment enclosures. You dont know how many or what size wires will have to be pulled into the conduit. If you install the largest available, this is trade size _____. ------CORRECT ANSWER--------------- 4 The largest trade size Schedule 80 PVC available that can be installed between two big pull boxes is ______. ------CORRECT ANSWER------------- -- 6 The maximum cross-sectional area that can be occupied by conductor in a 40 - foot run of conduit is 53% where the conduit contains ______ conductors. ------CORRECT ANSWER--------------- 1 What minimum size box (or box assembly) is required to contain the following? Exterior MC cable connectors are used on the cables. Two-10/2 with ground MC cables plus One- 12/2 with ground MC cable One- 30 amp 240-volt single receptacle and One- 20 amp 120- volt single receptacle ------CORRECT ANSWER---------------4 x 2 1/8 square box with a 4.1 cu. in. two-gang plaster ring A switch box will contain the following (one) isolated ground receptacle (one) 12/2 with ground AC cable (BX) with exterior connector
The shallowest switch box you can use for this installation is 3"x 2"x _______." ------CORRECT ANSWER---------------2 1/ When spray application equipment cannot be operated unless the exhaust ventilation system is operating and functioning properly and spray application is automatically stopped if the exhaust ventilation system fails the system is said to be ______. ------CORRECT ANSWER--------------- interlocked Vertically- mounted SPDT swithces shall be ON when in the ______ position.
The smallest circuit breaker that can be installed in a panel is ____ amp. The circuit supplies power to a 240-volt, single-phase, 5.8 KW, 50-gallon water heater. ------CORRECT ANSWER--------------- 30 A 100-gallon water heater is to be installed to supply hot water to the restrooms in an office building. The water heater is rated for 9.8 KW at 240 volts 1- phase. The minimum size THHN/THWN copper wire that can be installed between the required disconnect switch and the water heater is _____ AWG. ------CORRECT ANSWER--------------- 6 A unit switch is the ON/OFF switch on an appliance that disconnects all ____ conductors. ------CORRECT ANSWER---------------ungrounded A magnetic field is made up of invisible lines of force called ______ ------ CORRECT ANSWER---------------magnetic flux Where operating in the United States, AC voltage reaches a negative peak _____ times during one second. ------CORRECT ANSWER--------------- 60 Anex _____ in the NEC contains examples of load calculations for dwellings. ------CORRECT ANSWER---------------D Which of the installations listed below would be a wet location?
Which of the following is an example of a bare conductor?
i. two single-pole circuit breakers without handle ties ii. two single-pole circuit breakers with identified handle ties iii. a 2-pole circuit breaker ------CORRECT ANSWER---------------ii or iii only Which of the following is a type of circuit condition? i.short circuit ii. overload ------CORRECT ANSWER---------------i and ii A 20-amp multiwire branch circuit is connected to breakers 1 and 3 in a 120/208 volt 3 phase 4 wire panelboard. _____ if the "hot" from breaker 3 and the neutral are connected to a 2000-watt lighting fixture load. ------ CORRECT ANSWER---------------The load will operate normally and the breaker will not trip When ____ touch together this is a short circuit.
Your only available grounding electrode is the metal underground water pipe from the water utility. You are required by the NEC to have one other grounding electrode for your service. Which of the following driven electrodes could you use? ------CORRECT ANSWER---------------10 ft of trade size 1 rigid metal conduit Your only available grounding electroe is the metal underground water pipe from the water utility. You are required by the NEC to have one other grounding electrode for your service. You could use which of the following driven electrodes?
In a 60 Hz circuit, containing a 12 uf capacitor, the capacitive reactance is ____ ohms. ------CORRECT ANSWER---------------221. In a circuit with 25 ohms resistance and 50 ohms capacitive reactance, the impedance is ______ ohms. ------CORRECT ANSWER---------------55. At a recreational vehicle park, electrical service feeders shall be calculated on basis of not less than 600 volt-amperes per site when equipped with _________. ------CORRECT ANSWER---------------20a supply facilties with only one dedicated tent site In an AC circuit the total opposition to current flow is referred to as ______. ------CORRECT ANSWER---------------Impedance (z) True power is measure in ______ ------CORRECT ANSWER--------------- watts _______ surrounds the windings in typical "pole-mounted" transformers. --- ---CORRECT ANSWER---------------oil In reality, transformer efficiency can never be 100% because of ______.
You need to change from 240 volts to 480 volts to operate a piece of equipment that will require 25 KVA at 480 volts. You must use a transformer that is built specifically for step-up applications. T/F ------ CORRECT ANSWER---------------false A square D transformer with a nameplate rating of 240/480- V primary and 120/240 volt secondary can be connected to a 2-pole breaker in a _______ panelboard and deliver nameplate-rated voltage to a load.
The ______ rating is the ampere rating or setting of the over current device protecting the conductors. ------CORRECT ANSWER---------------branch circuit General lighting loads for dwelling units are calculated at ______ VA per square foot. ------CORRECT ANSWER--------------- 3 Article 220 required that each single or multiple receptacle on a single strap be calculated at ______ VA ------CORRECT ANSWER--------------- 180 For a single-family dwelling with six appliance loads, demand factors may be applied to ______ of these loads using the standard calculation. ------ CORRECT ANSWER---------------all six Using the standard calculation, the total load for household clothes dryers is computed at ______ VA or the nameplate rating whichever is higher. -----