ICC Mechanical Exam Practice Questions Part 1
with verified answers
1.Exhaust ducts under positive pressure, chimneys, and vents may not ex-
tend into or pass through . Exceptions ignored.:
plenums and ducts
2. systems are permitted to be
backfilled prior to inspection.: Ground-source heat pump loop
3.Air necessary for complete combustion of a fuel, including theoretical
air and excess air.: Combustion Air
4.Equipment and appliances installed at grade level must be supported on a
level concrete slab or other approved material extending not less than 3
inches above adjoining grade or must be suspended not less than
above adjoining grade. Such support shall be in accordance with the man-
ufacturer's installation instructions.: 6 inches
5.Air removed from a conditioned space and intended for reuse as
supply air.: Recirculated Air
6.For buildings containing dust, stock and refuse collectors and separators
such systems as centrifugal separators, bag filter systems and similar de-
vices, those devices and associated supports must be constructed of non-
combustible materials and must be located on .
Exceptions ignored.: the exterior of the building or structure
7.An installer has an 80,000 Btu per hour input fan-assisted appliance that
must be installed using 10 feet of lateral connector attached to a 30-foot-
high Type B vent. Two 90-degree elbows are needed for the installation. Can
a single-wall metal vent connector be used for this application?: No
8.On a liquid fuel oil system the outer ends of vent pipes must terminate in a
.: weatherproof vent cap or fitting or be
provided with a weatherproof hood
9.Ventilation must be provided in an approved manner in battery-charging
areas for powered industrial trucks and equipment .
Exceptions ignored.: to prevent a dangerous accumulation of vapor
pressure
10.The installation of fuel gas distribution piping and equipment, fuel gas-
fired appliances and fuel gas-fired appliance venting systems is regulated
by the .: International Fuel Gas
Code
pf3
pf4
pf5
pf8

Partial preview of the text

Download ICC Mechanical Exam Practice Questions Part 1 with verified answers and more Exams Nursing in PDF only on Docsity!

1 /

ICC Mechanical Exam Practice Questions Part 1

with verified answers

1.Exhaust ducts under positive pressure, chimneys, and vents may not ex- tend into or pass through. Exceptions ignored.: plenums and ducts

  1. systems are permitted to be

backfilled prior to inspection.: Ground-source heat pump loop 3.Air necessary for complete combustion of a fuel, including theoretical air and excess air.: Combustion Air 4.Equipment and appliances installed at grade level must be supported on a level concrete slab or other approved material extending not less than 3 inches above adjoining grade or must be suspended not less than above adjoining grade. Such support shall be in accordance with the man- ufacturer's installation instructions.: 6 inches 5.Air removed from a conditioned space and intended for reuse as supply air.: Recirculated Air 6.For buildings containing dust, stock and refuse collectors and separators such systems as centrifugal separators, bag filter systems and similar de- vices, those devices and associated supports must be constructed of non- combustible materials and must be located on. Exceptions ignored.: the exterior of the building or structure 7.An installer has an 80,000 Btu per hour input fan-assisted appliance that must be installed using 10 feet of lateral connector attached to a 30-foot- high Type B vent. Two 90-degree elbows are needed for the installation. Can a single-wall metal vent connector be used for this application?: No 8.On a liquid fuel oil system the outer ends of vent pipes must terminate in a .: weatherproof vent cap or fitting or be provided with a weatherproof hood 9.Ventilation must be provided in an approved manner in battery-charging areas for powered industrial trucks and equipment. Exceptions ignored.: to prevent a dangerous accumulation of vapor pressure 10.The installation of fuel gas distribution piping and equipment, fuel gas- fired appliances and fuel gas-fired appliance venting systems is regulated by the .: International Fuel Gas Code

2 / 11.2x12 nominal ceiling joists 12 feet long will need to be notched to ac- commodate an air duct, if the notch is at the top of the joists and not in the center 1/3 of the joists. What is the maximum allowable depth of the notches in inches?: 1.875 inches 12.Ducts and air transfer openings are required to be protected with a min- imum Class II, smoke damper complying with the Interna- tional Building Code.: 250 degrees

4 / 24.Plastic fire sprinkler piping exposed within a plenum must be used only in systems.: wet pipe 25.For combustion, ventilation and dilution air openings used to connect in- door spaces each opening must have a minimum free area of 1 square inch per 1,000 Btu/h of the total input rating of all appliances in the space, but not less than 100 square inches. One opening must commence within of the top and one opening shall commence within of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (76 mm).: 12 inches, 12 inches 26.The requirements for combustion and dilution air for gas-fired appliances must be in accordance with the .: International Fuel Gas Code 27.A factory-applied name-plate must be affixed to ap- pliances on which there must appear in legible lettering, the manufacturer's name or trademark, the model number, serial number and the seal or mark of the approved agency.: permanent 28.Where a smoke detection system is installed in all areas served by the duct in which the damper will be located, the smoke dampers is permitted to be controlled by the smoke detection system. True or False?: True 29.The International Mechanical Code regulates the design, installation, maintenance, alteration and inspection of mechanical systems that are .: permanently installed and utilized to pro- vide control of environmental conditions and related processes within buildings 30.Ducts discharging combustible material directly into any must conform to the requirements of NFPA 82.: - combustion chamber 31.Return air for a forced-air heating and cooling systems must not be taken from: Exceptions ignored.: a kitchen, garage, mechanical room, boiler room or furnace room or unconditioned attic 32.Where a smoke damper is installed within a duct, a smoke detector must be installed inside the duct or outside the duct with sampling tubes protruding into the duct. The detector or tubes within the duct must be installed within of the smoke damper.: 5 feet 33.A 500 sq. ft. room contains a refrigeration system and is occupied un- der normal conditions by 5 people; the mechanical ventilation system must exhaust a minimum of cubic feet per minute. Disregard any

5 / temperature rise due to the equipment.: 250 cubic feet per minute 34.Duct systems constructed of approved materials that penetrate nonfire- resistance-rated floor assemblies must be protected by which of the following

7 / 40.Where ducts used for cooling are externally insulated, the insulation must be covered with a or aluminum foil having a minimum thick- ness of 2 mils. Exception ignored.: vapor retarder 41.The design and operation of an exhaust system transporting flammable contaminants must be such that the contaminants are diluted in noncontami- nated air to maintain concentrations in the exhaust flow below of the contaminant's lower flammability limit.: 25 percent 42.A wall-mounted canopy hood is 4 feet long is mounted in a commercial kitchen. What is the required CFM rating require for the exhaust fan in this hood.: 1600 CFM 43.Interior spaces intended for human occupancy must be provided with active or passive space-heating systems capable of maintaining an indoor temperature of not less than at a point 3 feet above floor on the design heating day. Exceptions ignored.: 68 degrees 44.Mechanical systems located in an elevator shafts .: are not allowed 45.The minimum clearance to combustibles in inches for an exhaust vent ex- pelling hazardous gases greater than 100oF but less than 600oF is .- : 12 inches 46.Screens may not be installed at the duct termination for a clothes dryer vent. True or False?: True 47.Regarding the pressure test to be used for fuel gas systems, test duration may not be less than of pipe volume or fraction thereof. When testing a system having a volume less than 10 cubic feet or a system in a single-family dwelling, the test duration must be not less than 10 minutes.: 1/2 hour for each 500 cubic feet 48.Mechanical systems that are a part of buildings or structures moved into or within the jurisdiction do not need to comply with the provisions of the code for new installations. Exceptions ignored. True or False?: False 49.Oil-fired appliances must be provided with in accordance with NFPA 31.: combustion air 50.Energy recovery ventilation systems may not be used in which the fol- lowing system(s): Exceptions ignored.: Hazardous exhaust systems covered in Section 510. Dust, stock and refuse systems that convey explosive or flammable vapors, fumes or dust. Smoke control systems covered in Section 513.

8 / Commercial kitchen exhaust systems serving Type I and Type II hoods and clothes dryer exhaust systems covered in Section 504.