Docsity
Docsity

Prepare for your exams
Prepare for your exams

Study with the several resources on Docsity


Earn points to download
Earn points to download

Earn points by helping other students or get them with a premium plan


Guidelines and tips
Guidelines and tips

Guide to Conduits and Fittings for Traffic Signal and Lighting Systems, Exams of Construction

Information on the standards and requirements for conduits and fittings used in traffic signal and lighting systems. It covers the types of conduits, their installation requirements, and the specifications for different types of conduits and fittings. The document also discusses the use of non-metallic conduits, such as PVC and HDPE, and their installation methods.

Typology: Exams

2021/2022

Uploaded on 09/27/2022

geryle
geryle 🇺🇸

4.5

(23)

277 documents

1 / 8

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
SIGNALS AND LIGHTING FIELD GUIDE
Conduits and Fittings
12-1
CHAPTER 12 CONDUITS AND FITTINGS
CONDUITS AND FITTINGS
The standards and requirements for conduits and fittings used for traffic control signal and
lighting systems are presented in this chapter.
12.1 Conduits
A conduit is defined as a tube or duct for enclosing wires or cables.
12.1.1 GENERAL REQUIREMENTS FOR NON-METALLIC CONDUIT
MnDOT allows the use of either rigid polyvinyl chloride (PVC) conduit (rigid sectional lengths) or
high-density polyethylene (HDPE) (continuous length) conduit. All rigid PVC and HDPE conduit
and fittings must be Schedule 80 and listed by a Nationally Recognized Testing Laboratory (NRTL)
as being compliant with the requirements of UL 514B and UL 651 for underground use. All non-
metallic conduit must be either red or gray in color. See contract documents for the specific
requirements for all non-metallic conduits.
Installation Requirements
Before cables and conductors are installed, standard non-metallic conduit end bells must be
installed to prevent damage to the cables and conductors. The contractor must trim the inside
and outside of cut ends to remove rough edges. Cut ends of sectional conduit must butt or come
together for the full circumference thereof. All open ends of non-metallic conduit must be
immediately capped to keep moisture and debris out.
When rigid PVC conduit sections are installed using the directional boring method the rigid PVC
conduit “sections” must be pre-glued at least six hours prior to installation under roadway
Figure 12-1: Rigid PVC Sectional and Continuous Length (HDPE) Conduit
pf3
pf4
pf5
pf8

Partial preview of the text

Download Guide to Conduits and Fittings for Traffic Signal and Lighting Systems and more Exams Construction in PDF only on Docsity!

12-

CHAPTER 12 – CONDUITS AND FITTINGS

CONDUITS AND FITTINGS

The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter.

12.1 Conduits

A conduit is defined as a tube or duct for enclosing wires or cables.

12.1.1 GENERAL REQUIREMENTS FOR NON-METALLIC CONDUIT MnDOT allows the use of either rigid polyvinyl chloride (PVC) conduit (rigid sectional lengths) or high-density polyethylene (HDPE) (continuous length) conduit. All rigid PVC and HDPE conduit and fittings must be Schedule 80 and listed by a Nationally Recognized Testing Laboratory (NRTL) as being compliant with the requirements of UL 514B and UL 651 for underground use. All non- metallic conduit must be either red or gray in color. See contract documents for the specific requirements for all non-metallic conduits.

Installation Requirements Before cables and conductors are installed, standard non-metallic conduit end bells must be installed to prevent damage to the cables and conductors. The contractor must trim the inside and outside of cut ends to remove rough edges. Cut ends of sectional conduit must butt or come together for the full circumference thereof. All open ends of non-metallic conduit must be immediately capped to keep moisture and debris out.

When rigid PVC conduit sections are installed using the directional boring method the rigid PVC conduit “sections” must be pre-glued at least six hours prior to installation under roadway

Figure 12 - 1 : Rigid PVC Sectional and Continuous Length (HDPE) Conduit

12-

surfaces. Long-line couplings must be used when rigid PVC conduit sections are installed under roadway surfaces.

HDPE continuous length conduit must not be spliced under roadway surfaces. HDPE continuous length conduit must not be used between concrete foundations and the nearest handhole.

Underground conduit runs must have provisions for drainage of moisture. Horizontal conduit runs must be sloped to drain at a rate of not less than 0.25 percent, and all low points must be drained. At the low points (not at the open ends of conduit runs) a standard tee conduit fitting must be installed and a nipple at least six inches long must be extended into a hole approximately two feet square by two feet deep and backfilled with crushed rock or approved granular material.

The contractor must pull cables and conductors through the non-metallic conduit in such a manner as not to damage the conduit due to pull rope abrasion. The contractor will be required to pull a ground wire through the conduit system as required by the contract documents.

Additional considerations include:

  • The material for all conduit bushing grounding lugs used on RSC conduit must consist of stainless steel, brass, copper or bronze with lay in ground lugs.
  • Transformer to source of power (SOP): 2-inch RSC or as specified in the contract documents.
  • Liquid Tight Flexible Non-Metallic Conduit (LFNC-B) - Specification 3804: MnDOT primarily uses liquid tight flexible non-metallic conduit when installing bridge underpass luminaires. Installation requirements are covered in 2565.3D.

12.1.2 TYPES OF CONDUIT FOR TRAFFIC CONTROL SIGNAL CONSTRUCTION MnDOT uses three types of conduits in traffic control signal construction:

  • Rigid Steel Conduit - Specification 3801
  • Non-Metallic Conduit - Specification 3803
  • PVC Coated Hot Dipped Galvanized Rigid Steel Conduit - Specification 3805: MnDOT uses PVC Coated RSC on bridges. The conduit can hang under the bridge deck and will be encased in concrete when required. Installation requirements are covered in Specification 2565.3D.

12.1.3 TYPES AND SIZES OF CONDUIT FOR LIGHTING SYSTEM CONSTRUCTION Lighting plans will indicate the size of conduit to be used in the construction of a lighting system and the following are the typical sizes of conduit used:

  • Median Barrier: 1-1/2-inch rigid PVC conduit.
  • Under traveled roadway: 4-inch rigid PVC conduit, or HDPE conduit marking each end with a red ball locator (See Chapter 12 for ball locator information).
  • Bridges: 1-1/2-inch PVC coated hot dipped galvanized rigid steel conduit and retaining walls use 1-1/2-inch rigid PVC conduit or as specified in the contract documents.
  • PVC conduit may also be used in rest areas and/or in plans within city limits. Conduit size will be according to the plan.

12-

Conduits attached to other structures must be secured as indicated in the contract documents to the satisfaction of the engineer.

Underground (2565.3D) Underground conduits must be placed no less than 18 inches below the surface of any ground area and not less than 24 inches below any roadway surface. It should be noted that the depth of the conduit is measured from the top of the pipe. For example, a trench for a 4-inch conduit is 22 inches from the finished ground to the bottom of the trench.

Conduits placed under railroad tracks must be placed no less than 57 inches below the bottom of the ties or as required by the railroad company.

For RSC and rigid PVC conduit, trenching is the accepted method of conduit installation except when the conduits are being installed under existing roadways. Conduits must not be placed until the trench has been inspected.

Except for under existing pavements, HDPE (continuous length) conduit must be placed by trenching, vibratory plow with feed blade or directional boring.

If installing conduit under an existing roadway using a method other than directional boring and a distortion more than 1/4-inch is created in the existing roadway surface due to conduit installation, the contractor must remove the distortion and restore at no expense to the department the roadway surface to its original condition.

Figure 12 - 5 : Underground Conduit Installation

Figure 12-6: Conduit under Railroad Tracks

Figure 12-8: Trenching

Figure 12-7: HDPE Conduit

Figure 12-4: Conduit Attached to Bridge

12-

Direct buried lighting cable must be installed in rigid PVC or HDPE conduit under paved surfaces, including concrete, bituminous, and brick pavers.

If boring operations through a roadbed are abandoned for any reason, the voids must be grouted at the contractor’s expense and to the satisfaction of the engineer.

For handholes used on lighting systems, the contractor must install a 36-inch rigid PVC conduit stub out with the appropriate end bell for all direct buried lighting cable entering a handhole.

Position conduit terminating in concrete foundations, and equipment pads so the conduit extends inside the pole bases, structure bases, or service cabinets as indicated in the standard plates or plan details. Slope the conduit away from the foundation and toward the handhole opening for drainage.

Conduits that are stubbed out underneath the foundation for future use must extend 18 inches to 24 inches beyond the foundation or sidewalk in the direction specified by the engineer, and capped on both ends with standard pipe caps. After the cap is secured, a permanent marker should be used to draw an arrow, on the cap, indicating the direction of the conduit (as indicated in Figure 12-13).

Figure 12 - 10 : Conduit Positioning

Figure 12 - 11 : Direction of Conduit Arrow

Figure 12 - 9 : Conduit Stub Out/End Bell

2545.3G. Install direct buried lighting cable in rigid PVC or HDPE conduit if located under bituminous, concrete, Figure 12 - 4 : Conduit Requirements for Direct Buried Lighting Cable Under Hard Surfaces

12-

The open ends of conduits in a cabinet or foundation must be sealed in accordance with 2565.3D.2.b.

After the installation of the cables and conductors use a duct seal compound NRTL classified under general use tapes. This prevents moisture from entering the cabinet or pole. The sealant also helps in preventing rodents from entering the foundation through the conduit system.

RSC Joints (2565.3D) When standard length RSC conduit is cut the end must be threaded and reamed to remove burrs and rough edges. Field cuts must be made square and true so that all ends joined by coupling butt together for the full circumference. This provides an electrical bonding and grounding connection throughout the entire length of the conduit run.

If the galvanized coating on the conduit is damaged during handling or installation, the damaged areas must be painted with MnDOT approved paint to the satisfaction of the engineer.

Existing Conduit (2565.3D) If the existing underground conduit is incorporated into a new traffic control signal or lighting system, it must be cleaned and blown out with compressed air before the new wires are installed. If a new handhole is installed into an existing conduit run, the conduit must be cut, threaded and extended into the new handhole as directed by the engineer. A new bushing with an integral lug and ground wire must be installed and the sides of the handhole must be made water tight before the installation of any new wires. Thread less couplings and bushings are not permitted unless otherwise authorized by the engineer.

Figure 12 - 6 : Conduit Duct Seal Compound

Figure 12 - 7 : Threading and Reaming the RSC Conduit End

Figure 12-18: Existing Underground Conduit

12-

Expansion and Deflection/Expansion Fittings for Conduits used on Bridges (2565.3D.7 & 3839) Because bridges are subjected to flexing, expansion and contraction, special PVC coated expansion and expansion/deflection conduit fittings as well as hangers are required. Improper installation of conduits can cause severe damage to the electrical system and may cause damage to the bridge structure itself. The expansion fitting provides eight inches of linear movement. The deflection/expansion fitting provides 3/4 of an inch of movement in any direction.

MnDOT requires contractors to obtain a separate installation certification training from at least one PVC coated RSC conduit manufacturer.

Repair of damaged PVC coating shall be made in accordance with the conduit manufacturer’s repair requirements.

All conduits must be attached to bridge as specified in the contract documents.

12.2 Chapter 12 Resources

  • MnDOT Standard Specifications for Construction 3801, 3803, 2565.3D, 2545.3G.2, 2545.1C, 2565.1C, 2545.3.R, 2565.3.D.4.b, 2565.3D.7 & 3839
  • National Electrical Code (NEC)

Figure 12 - 19 : Expansion Fitting

Figure 12 - 20 : Deflection/Expansion Fitting